Field-Programmable Pressure Switch/Transducer - TDEPD Series

• Pressure Range: up to 10,000 psi (689 bar)
• Accuracy: 0.5% of maximum operating pressure
• Maintenance Mode (redundant sensing notification)
• Power supply: 10.5 VDC to 28 VDC
• 4-digit, bi-color display (red or green)
• Display: 360 ° scrolling or lock in location
• Pressure port: ¼-inch NPT, 7/16-20 UNF, G 1/4

  • Model Number: TDEPD Series
  • Data Sheet: Date Sheet File
Quantity:
- +
  • Field-Programmable Pressure Switch/Transducer
  • Field-Programmable Pressure Switch/Transducer
  • Field-Programmable Pressure Switch/Transducer
Mouse over image to zoom

Product Specification

TDEPD Series Pressure Transducer DESCRIPTION
What makes the patented TDEPD Series stand apart is the unique LED display - which allows for 360° scrolling, or you can lock the display in one location. It also features field-programmable set points and hysteresis.

Because it is built on Transducers Direct’s TD1000 technology, the TDEPD Series incorporates redundant sensing elements,allowing for notification that the sensor needs to be replaced should one of the sensing elements fail (maintenance mode), eliminating operational downtime.

The TDEPD Series pressure switch/transducer comes standard with one digital output and optional analog output available. Unit operates from 10.5 to 28 VDC, and is IP67 certified.

TDEPD Series Pressure Transducer FEATURES
• Maintenance Mode (redundant sensing notification)
• Power supply: 10.5 VDC to 28 VDC
• 4-digit, bi-color display (red or green)
• Display: 360 ° scrolling or lock in location
• Pressure port: ¼-inch NPT, 7/16-20 UNF, G 1/4
• Digital outputs : 250 mA max (PNP) or 200 mA max (NPN), and/or optional analog output: up to 10 VDC or up to 20 mA (field selectable)
• Wide variety of pressure ranges up to 10K psig
• Spike Monitoring Technology™ (SMT)

TDEPD Series Pressure Transducer SPECIFICATIONS

Performance

Performance @ 25°C (77°F)

Accuracy

0.5% of maximum operating pressure

Overange Protection

2x Rated Pressure or optional 4x and 10x

Pressure Range

see ordering chart - up to 10,000 psi (689 bar)

Burst Pressure

5x or 20,000 psi, whichever is less

Pressure Cycles

>100 million

Update Time

<=1msec

 

Environmental Data

Temperature

 

Compensated Temperatures

-40 to 85°C (-40 to 185°F)

Operating Temperatures

-40 to 100°C (-40 to 212°F)

Storage

-40 to 125°C (-40 to 257°F)

TEB

1% BFSL (includes:Non-linearity, Hysteresis and Non-repeatability), analog output

Long Term Drift

0.2% FS/year (non-cumulative)

Shock

50g, 11 ms, 1/2 sine

Vibration

10g, peak, 20 to 2400 Hz

EMI/FRI Protection

Yes

Rating

Up to IP-67

 

Mechanical Configuration

Pressure Connections

1/4” NPT Male, 7/16-20 UNF, G1/4 Male

Wetted Material

17-4PH stainless steel (for other materials consult factory)

Electrical Connection

M12 (5-pin)

Case

(housing) 304 stainless steel and high-impact polycarbonate (display)

 

Electrical Data

Power Supply

10.5-28VDC

Switch/Analog Output

10.5 VDC to 28 VDC at 250 mA max (PNP) or 200 mA max (NPN) (digital), 

Field-programmable-- voltage up to 10 VDC or current up to 20mA

Output Impedance

<100 Ohms, Nominal

Current Consumption

30 mA @ 24 V / voltage output

40 mA @ 12 V / voltage output

50 mA @ 24 V / current output

60 mA @ 12 V / current output

Output Noise

<2mV RMS

Reverse Polarity Protection

Yes

Set Points

No set points in vacuum range, 5 psi min set point with <100 psi range,

10% of configured pressure min set point with > 100 psi range

Spike Counter

Press button # 1 for 10 seconds to view quantity of pressure spikes 

and the highest spike seen. 

Zero/Tare display

Press button #2 for 10 sec. If the pressure reading on the display is between -14.7 

and 128 psi, the display will change to zero (0). If pressure is above 128 psi, display 

will not change.


TDEPD Series Pressure Transducer ORDERING


If you cannot find what you want, you can entrust ISweek to source for you. Just click:

Sourcing Service